Electrician: Voltage Drop Percent

Excel Formulas › Electrician

All versions

Long runs cost voltage. The NEC recommends keeping branch-circuit drop under 3%, and the arithmetic is short enough to keep in a spreadsheet next to your wire chart.


Quick formula: Voltage lost, divided by supply voltage:
=ROUND(2*B2*C2*D2/1000/E2,4)

A 120 ft run at 20 A on #12 copper (1.93 Ω/1000 ft) at 240 V drops 9.26 V — 3.86%, over the 3% guideline.

Functions used (tap for the full reference guide):

The example

Three runs on the same job, each with its own length, load, and conductor.

ABCDEF
1RunLength (ft)AmpsOhms/1000ftVoltsDrop %
2Shop feeder120201.932403.86%
3Well pump220121.212402.66%
4Yard lights9063.071202.76%

The formula

The 2 accounts for the current travelling out and back; the 1000 converts the resistance table units:

=ROUND(2*B2*C2*D2/1000/E2,4) // 2 x length x amps x ohms-per-1000ft / 1000 / supply volts

How it works

Build it one factor at a time:

  1. 2*B2 doubles the run length — current flows down the hot and back on the neutral, so the wire is twice as long electrically.
  2. *C2*D2/1000 applies Ohm's law: amps times total resistance gives volts lost. Dividing by 1000 matches the per-1000-feet units in the wire table.
  3. /E2 turns volts lost into a fraction of supply voltage.
  4. ROUND(...,4) keeps four decimals so the percent format shows two.

For three-phase runs replace the 2 with 1.732. Everything else in the formula stays put.

Try it: interactive demo

Interactive

Enter the run length, load, conductor resistance, and system voltage.

Variations

Flag runs over 3%

Let the sheet tell you when to go up a wire size.

=IF(F2>0.03,"Upsize","OK")

Volts lost instead of percent

Sometimes the raw number is what the inspector wants.

=2*B2*C2*D2/1000

Pitfalls & errors

Enter the one-way run length. The formula already doubles it — entering the round trip doubles the drop and sends you up two wire sizes for nothing.

Aluminium has roughly 1.6 times the resistance of copper of the same size. Keep separate resistance columns rather than fudging one number.

Practice workbook

📊
Download the free Electrician: Voltage Drop Percent practice workbook
Edit the yellow length, amps, ohms, and volts cells; drop % recalculates.

Frequently asked questions

Is 3% a hard code limit?
No — in the NEC it appears as an informational note, not a mandatory rule, for branch circuits (with 5% total including the feeder). Local amendments and specs often make it mandatory, so check before you cut wire.
Where do the ohms-per-1000-feet numbers come from?
NEC Chapter 9, Table 8 for DC resistance, or Table 9 for AC. Copy the sizes you actually stock into a lookup table and point the formula at it.

Stop fighting formulas. Learn them in a day.

This recipe is one of hundreds of real-world formulas we teach. Our Excel Formulas & Functions class covers lookups, logic, text, and dynamic arrays hands-on — live in Dallas–Fort Worth, Houston, Austin, Oklahoma City, Denver, or online.

See the Formulas & Functions Class

Related formulas: Electrician: Wire Run Cost · Electrician: Panel Load Percent · Solar: DC/AC Ratio

Function references: ROUND